Use the AWC Special Design Provisions for Wind and Seismic,…

Questions

Use the AWC Speciаl Design Prоvisiоns fоr Wind аnd Seismic, 2015 Edition аnd ASD procedures to answer the following question.A building is exposed to a transverse load of wU = 425 lb/ft due to wind. Assume this load was determined from the ASD load combinations, i.e. do not apply the load combinations to it. The wood structural panel is 7/16-in. thick 24/16 span-rated sheathing blocked. Nails are 8d common and spaced every 6 in. at diaphragm boundaries and all panel edges utilizing a single row of nails. Is this design adequate for the transverse load? Let L = 60 ft and b = 40 ft.